1/03 UDC 6300 Process Controller Product Manual 237
6.12 Restoring Factory Calibration, Continued
Procedure, continued
Table 6-10 Restoring Factory Calibration, continued
Step Operation Press Action/Result
INPUTS 1, 2, 3, OR 4
3
Enter
“INPUT
1,2,3,4” Setup
Group
SET
UP
Until you see:
Upper Display
Lower Display
SET UP
INPUTn
n = 1, 2, 3, or 4
FUNC
L1/L2
Until you see:
Upper Display
Lower Display
XMITTERn
n = 1, 2, 3, or 4
Current Selection
or
to change the current selection to
another selection.
FUNC
L1/L2
Until the lower display rolls through the
rest of the functions and returns to
Upper Display
Lower Display
XMITTERn
n = 1, 2, 3, or 4
New Selection
or
Until you change the input selection in
the upper display back to the proper
selection. You will see:
Upper Display
Lower Display
Original input
selection that
matches your
type of sensor.
XMITTERn
n = 1, 2, 3, or 4
GO TO STEP 5.
Continued on next page