124 UDC 6300 Process Controller Product Manual 1/03
4.13 Options Set Up Group, Continued
Table 4-12 Option Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
DIG 1 COMB
DIGITAL INPUT 1 COMBINATIONS - These selec-
tions can be used with any selection from DIG IN1.
DISABLE
DISABLE - Disables combination function.
+ To PID2
ANY DIGITAL INPUT SELECTION PLUS TO PID
SET TWO – Contact closure puts the controller into
PID SET 2.
+ To DIR
ANY DIGITAL INPUT SELECTION PLUS TO
DIRECT CONTROL – Contact closure puts the
controller into DIRECT CONTROL.
+ToSP2
ANY DIGITAL INPUT SELECTION PLUS TO
LOCAL SETPOINT TWO — Contact closure puts
the controller into local setpoint 2.
ADT1
ANY DIGITAL INPUT SELECTION PLUS DISABLE
ADAPTIVE TUNE— Contact closure disables
Adaptive Tune on Loop 1.
+ToSP1
ANY DIGITAL INPUT SELECTION PLUS TO
LOCAL SETPOINT ONE — Contact closure puts
the controller into local setpoint 1.
To RUN
ANY DIGITAL INPUT SELECTION PLUS RUN
SETPOINT RAMP — Contact closure switches to
RUN if Setpoint Ramp.
DIG IN 2
DIGITAL INPUT TWO SELECTIONS — Same
selections as DIG IN1. Digital Input 2 is reserved for
Loop 2 parameters when Two Loops or Internal
Cascade is configured.
DIG 2 COMB
DIGITAL INPUT 2 COMBINATIONS - These
selections can be used with any selection from
DIG IN2.
Table 4-12 continued on next page