90 UDC 6300 Process Controller Product Manual 1/03
4.6 Algorithm Data Set Up Group, Continued
Table 4-5 Algorithm Group Definitions, continued
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
IN ALG 2
NONE
WTD AVG
FFWD SUM2(applies only
to Loop 2)
A–B DIV C *
HI SELECT
LO SELECT
MUL DIV
MULTIPLY
MUL DIV
MULTIPLY
FFWD MUL2(applies only
to Loop 2)
INPUT ALGORITHM 2 - the selections from which to
choose are listed to the left.
The formulas are the same as shown for "IN ALG 1".
*
ATTENTION
Selection "A–B DIV C" algorithm
subtracts Input B with Ratio/Bias from Input A with
Ratio/Bias and divides the result by Input C with
Ratio/Bias using Engineering units.
Example
(A - B)
C
(Calc Hi - Calc Lo))
PV or SP = K
CONST K2
0.001 to 1000
WEIGHTED AVERAGE RATIO OR K CONSTANT
FOR MATH SELECTIONS - Only applicable for
algorithms "WTD AVG" or Math selections
"MUL DIV ", "MULTIPLY ", "MULT DIV", or
"MULTIPLY"
CALC HIGH
–999 to 9999
CALCULATED VARIABLE HIGH SCALING FACTOR
FOR INPUT ALGORITHM 2- Does not apply to
Feedforward Algorithms.
CALC LOw
–999 to 9999
CALCULATED VARIABLE LOW SCALING FACTOR
FOR INPUT ALGORITHM 2 - Does not apply to
Feedforward Algorithms.
ALG 2 IN A
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OUTPUT 1
OUTPUT 2
OTHER ALG
ALGORITHM 2, INPUT A SELECTION - will represent
one of the available selections.
ALG 2 IN B
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OUTPUT 1
OUTPUT 2
OTHER ALG
ALGORITHM 2, INPUT B SELECTION - will represent
one of the available selections.
ALG 2 IN C
NONE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
OTHER ALG
ALGORITHM 2, INPUT C SELECTION - will represent
one of the available selections.
Table 4-5 continued on next page