4.8 Output Algorithm Parameters Set Up Group
Introduction
This data deals with various output types in the controller, the Digital
Output Status, and the Current Duplex functionality.
Algorithm group
prompts
Table 4-7 lists all the function prompts in the "Output Algorithm" setup
group and their definitions.
Table 4-7 Output Algorithm Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
OUT ALG
The OUTPUT ALGORITHM lets you select the type
of output you want. Selections are model dependent.
For example, current output models cannot be
configured for Time Proportioning Simplex Output.
TIME
TIME SIMPLEX — This Output algorithm uses
Digital Output 3 for Time Proportional Control. The
output is updated per the Loop sampling rate
selection. Time Proportional Output has a resolution
of 4.44 msec. Cycle Time is adjustable from 1 to
120 seconds.
CURRENT
CURRENT SIMPLEX — Type of output using one
4 to 20 mA signal that can be fed into a positive or
negative grounded load of 0 to 1000 ohms. The
signal can be re-calibrated for any desired range
from 4 to 20 mA for 0 to 100% output.
TIME DPLX
TIME DUPLEX — This Output algorithm uses Digital
Outputs 3 and 4 for Duplex Time Proportional
Control. The outputs are updated per the Loop
sampling rate selection. Time Proportional Output
has a resolution of 4.44 msec. Cycle Time is
adjustable from 1 to 120 seconds.
CUR DPLX
CURRENT DUPLEX is similar to current simplex but
uses a second current output. The second output is
usually scaled so that zero and span correspond
with 0% and 50% output (cool zone). When the
output is 0 to 50%, the controller uses tuning
parameter set #2, when the output is 50 to 100% it
uses set #1.
Other prompts affected: "4-20 RNG”
CUR TIME
CURRENT/TIME DUPLEX (Digital Output 3 =
HEAT) is a variation of duplex with current active for
0 to 50% output (tuning set 2) and Time is active 50
to 100% output (tuning set 1).
Other prompts affected: "4-20 RNG”
TIME CUR
TIME CURRENT DUPLEX (Digital Output 3 =
COOL) is similar to "CUR-TIME" except that current
is active for 50 to 100% and Time is active for 0 to
50%.
Other prompts affected: "4-20 RNG”.
Table 4-7 continued on next page