1/03 UDC 6300 Process Controller Product Manual 177
5.12 Configure 2 Loop of Control
Select 2 loop
algorithm
The procedure in Table 5-24 shows you how select the 2 loop algorithm.
Table 5-24 Procedure for Selecting 2 Loop Algorithm
Step Operation Press Action
1
Select
Algorithm Set
Up Group
SET
UP
Until you see:
ALGORTHM
Lower Display
SET UP
Upper Displa
2
Select the PID
Loops
FUNC
L1/L2
to successively display the following
constants:
ALGORTHM
Lower Display
Upper Displa
1 LOOP
2LOOPS
CASCADE
or
To select 2 Loops or Cascade.
Select the output
algorithm for each
loop
See Subsection 5.11 for rules and regulations then follow the procedure in
Table 5-25.
Table 5-25 Procedure for Selecting Output Algorithm
Step Operation Press Action
1
Select Output
Algorithm Set
Up Group
SET
UP
Until you see:
OUT ALG
Lower Display
SET UP
Upper Displa
2
Select Loop 1
Algorithms
FUNC
L1/L2
to successively display the following
constants:
OUT ALG
Lower Display
Upper Displa
TIME
CURRENT
TIME DPLX
CUR DPLX
CUR TIME
TIME CUR
or
To select Loop 1 algorithm.
Table 5-5 continued on next page