218 UDC 6300 Process Controller Product Manual 1/03
6.2 Minimum and Maximum Range Values
Select the range
values
You should calibrate the controller for the minimum (0%) and Maximum
(100%) range values of your particular sensor.
Calibrate each input separately.
Select the Voltage or Resistance equivalent for 0% and 100% range
values from Table 6-1. Use these value when calibrating your controller.
Table 6-1 Voltage and Resistance Equivalents for 0% and 100% Range Values
Sensor Type PV Input Range Range Values
° F ° C 0% 100%
B Thermocouple
105 to 3300 41 to 1815 0 mV 13.763 mV
E Thermocouple
-454 to 1832 –270 to 1000 –9.835 mV 76.358 mV
J Thermocouple
0 to 1600 –18 to 871 –0.885 mV 50.059 mV
K Thermocouple
0 to 2400 –18 to 1316 –0.692 mV 52.939 mV
NiNiMoly T/C
32 to 2500 0 to 1371 –0.001 mV 71.330 mV
Nicrosil Nisil T/C
0 to 2372 –18 to 1300 –0.461 mV 47.502 mV
R Thermocouple
0 to 3100 –18 to 1704 –0.089 mV 20.275 mV
S Thermocouple
0 to 3100 –18 to 1704 –0.092 mV 17.993 mV
T Thermocouple
-300 to 700 –184 to 371 –5.341 mV 19.095 mV
W5W26 T/C
0 to 4200 –18 to 2316 –0.234 mV 37.066 mV
RTD (IEC=0.00385)
100 Ohms
100 Ohms (low)
200 Ohms
500 Ohms
-300 to 900
0 to 300
-300 to 900
-300 to 900
–184 to 482
–18 to 149
–184 to 482
–184 to 482
25.18
93.03
50.36
125.90
274.96
156.90
549.92
1374.80
Radiamatic (RH)
1400to3400 760 to 1871 0.99 mV 57.12 mV
Milliamps
4 to 20 mA 4 mA 20 mA
Millivolts
0 to 10 mV 0 mV 10 mV
10 to 50 mV 10 mV 50 mV
Volts
1 to 5 Volts 1 Volt 5 Volts
0 to 10 Volts 0 Volts 10 Volts