218 UDC 6300 Process Controller Product Manual 1/03
6.2 Minimum and Maximum Range Values
Select the range
values
You should calibrate the controller for the minimum (0%) and Maximum
(100%) range values of your particular sensor.
Calibrate each input separately.
Select the Voltage or Resistance equivalent for 0% and 100% range
values from Table 6-1. Use these value when calibrating your controller.
Table 6-1 Voltage and Resistance Equivalents for 0% and 100% Range Values
Sensor Type PV Input Range Range Values
° F ° C 0% 100%
B Thermocouple
105 to 3300 41 to 1815 0 mV 13.763 mV
E Thermocouple
-454 to 1832 –270 to 1000 –9.835 mV 76.358 mV
J Thermocouple
0 to 1600 –18 to 871 –0.885 mV 50.059 mV
K Thermocouple
0 to 2400 –18 to 1316 –0.692 mV 52.939 mV
NiNiMoly T/C
32 to 2500 0 to 1371 –0.001 mV 71.330 mV
Nicrosil Nisil T/C
0 to 2372 –18 to 1300 –0.461 mV 47.502 mV
R Thermocouple
0 to 3100 –18 to 1704 –0.089 mV 20.275 mV
S Thermocouple
0 to 3100 –18 to 1704 –0.092 mV 17.993 mV
T Thermocouple
-300 to 700 –184 to 371 –5.341 mV 19.095 mV
W5W26 T/C
0 to 4200 –18 to 2316 –0.234 mV 37.066 mV
RTD (IEC=0.00385)
100 Ohms
100 Ohms (low)
200 Ohms
500 Ohms
-300 to 900
0 to 300
-300 to 900
-300 to 900
–184 to 482
–18 to 149
–184 to 482
–184 to 482
25.18 Ω
93.03 Ω
50.36 Ω
125.90 Ω
274.96 Ω
156.90 Ω
549.92 Ω
1374.80 Ω
Radiamatic (RH)
1400to3400 760 to 1871 0.99 mV 57.12 mV
Milliamps
4 to 20 mA 4 mA 20 mA
Millivolts
0 to 10 mV 0 mV 10 mV
10 to 50 mV 10 mV 50 mV
Volts
1 to 5 Volts 1 Volt 5 Volts
0 to 10 Volts 0 Volts 10 Volts