106 UDC 6300 Process Controller Product Manual 1/03
4.9 Input 1 Through 4 Parameters Set Up Group
Introduction
These are the parameters required for Inputs 1 through 4; transmitter
characterization, high and low range values in engineering units, Ratio,
Bias, and Filter. Also, Deadtime (Input 3 only) and Xmitter 4 (Input 4
only).
Input 1 through 4
group prompts
Table 4-8 lists all the function prompts in the Input 1 through 4 setup
group and their definitions.
Table 4-8 Input 1 through 4 Group Definitions
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
XMITTERn
(n = 1, 2, 3, or 4)
ATTENTION
Change of input
characterization
selection results in
loss of any field
calibration and
restores factory
calibration of linear
range 1 to 5 Volts.
DISABLE
B TC
E TC
J TC
K TC
NNM
NIC TC
R TC
S TC
T TC
W TC
100 PT
100 PT LO
200PT
500PT
LINEAR
SQ ROOT
IN2 NO R/B (Xmitter 4
only)
TRANSMITTER CHARACTERIZATION — This
selection lets you instruct the controller to
characterize a linear input to represent a non-linear
one.
DISABLE - Disable Input
B TC - B Thermocouple
E TC- E Thermocouple
J TC- J Thermocouple
K TC- K Thermocouple
NNM- NiNiMo Thermocouple
NIC TC- Nicrosil Nisil Thermocouple
R TC- R Thermocouple
S TC- S Thermocouple
T TC- T Thermocouple
W TC- W Thermocouple
100 PT - 100 Ohm RTD High
100 LOW - 100 Ohm RTD Low
200PT- 200 Ohm RTD
500PT- 500 Ohm RTD
LINEAR - Linear*
SQ ROOT - Square Root*
IN2 NO R/B - allows analog input 2 signal (without
Input 2 Ratio or Bias) to be configured with Input 4
Ratio and Bias without need to use a physical analog
input for input 4.
* No Characterization
INn HI
(n = 1, 2, 3, or 4)
–999 to 9999
in Engineering units
INPUT n HIGH RANGE VALUE in engineering units.
Available only if Linear or Square Root transmitter
characterization is selected.
Scale the #1 input signal to the display value you
want for 100%.
EXAMPLE:
Actuation (Input) = 4 to 20 mA
Process Variable = Flow
Range of Flow = 0 to 250 Gal/Min
High Range display value = 250
Low Range display value = 0
Then 20 mA = 250 Gal/Min
The control setpoint will be limited by the range of
units selected here.
Table 4-8 continued on next page